| Guaranteed Technical Particulars in compliance with IEC 60502, 60060 & 60230 |
| Tests |
Parmeter ForEvaluation
|
Test Voltage
1.1 |
Hightest Voltage Umax (kV)
3.3 |
Result |
|
Insulation Resistance |
1 mn. 500 V Dc |
- |
- |
>103 |
A.C. High Voltage Test (Joint
Immersed In Water) |
5 min. |
3.5 |
6 |
No Breakdown & no Flashover |
Impulse Witstand Test at
Ambient Temperature |
10 Positive & 10 Negative |
8 |
12 |
No Breakdown & no Flashover |
| Insulation Resistance |
1 min. 500 V Dc |
- |
- |
>10 3 |
Heating Cycle Test in Water (for
Straight Through Joint) |
63 cycles
5 hrs. heating & 3 hrs. cooling
Conductor temperature 95°C |
- |
- |
No Breakdown & no Flashover |
Insulation Resistance after
Impact Test (Immersed) |
1 min. 500 V Dc |
- |
- |
>103 |
Impulse Withstand Test at
Elevated Temperature |
10 Positive & 10 Negative Conductor temperatur
95 to 100°C |
8 |
12 |
No Breakdown & no Flashover |
| D.C. High Voltage Test (Dry) |
5min |
15 |
21 |
No Breakdown & no Flashover |