Busbar insulation tubes, Heat Shrinkable ProductsCable End Sealing Caps, Cable End Caps Busbar Tubes, Cable Breakouts, heat shrink molded shapes, dip molded components Power cable accessories, Switchgear insulation products, Heat Shrink Tubings

Heat Shrinkable Tubes/Heat Shrink Sleeves Heat Shrink tubes,Non Tracking tube - INSULTUBE non tracking

Anti-Tracking Tubes
Anti Tracking Tubes

Heat Shrink Non Tracking Tubes are Used In Medium Voltage Cable Joints and terminations upto 36 KV. The tubes are produced from high quality non tracking cross linked polyolefin material that offers execptional insulation and long term service reliability.

  • Excellent anti - tracking performance and erosion resistance.
  • Hologen free, flame retardant.
  • Good Weather / UV resistance.
  • High resistance to chemical, solvent, corrosion and fungus.
SELECTION CHART

All dimensions are in mm

  • Code
  • D Min (mm)
  • d Max (mm)
  • T±10% (mm)
  • Spool length (mtr)
  • GAT 25/8
  • 25
  • 8
  • 2.5
  • 30
  • GAT 30/12
  • 30
  • 12
  • 2.5
  • 30
  • GAT 40/16
  • 40
  • 16
  • 3.0
  • 30
  • GAT 50/20
  • 50
  • 20
  • 3.0
  • 30
  • GAT 65/25
  • 65
  • 25
  • 3.0
  • 15
  • GAT 75/28
  • 75
  • 28
  • 3.0
  • 15
  • GHW 100/38
  • 100
  • 38
  • 3.0
  • 15
SELECTION CHART (Heavy Wall)
  • Code
  • D Min (mm)
  • d Max (mm)
  • T±10% (mm)
  • Length Max.(mtr.)
  • GAT (HW) 25/8
  • 25
  • 8
  • 5
  • 1.5
  • GAT (HW) 35/12
  • 35
  • 12
  • 5
  • 1.5
  • GAT (HW) 55/18
  • 55
  • 18
  • 5
  • 1.5
  • GAT (HW) 65/25
  • 65
  • 25
  • 5
  • 1.5
  • GAT (HW) 85/30
  • 85
  • 30
  • 5
  • 1.5
  • GAT (HW) 100/38
  • 100
  • 38
  • 5
  • 1.5
  • GAT (HW) 120/45
  • 120
  • 45
  • 5
  • 1.5
  • GAT (HW) 140/50
  • 140
  • 50
  • 5
  • 1.5
SELECTION CHART (Extra Heavy Wall)
  • Code
  • D Min (mm)
  • d Max (mm)
  • T±10% (mm)
  • Length Max.(mtr.)
  • GAT (EHW) 35/12
  • 35
  • 12
  • 7
  • 1.5
  • GAT (EHW) 55/18
  • 55
  • 18
  • 7
  • 1.5
  • GAT (EHW) 65/25
  • 65
  • 25
  • 7
  • 1.5
  • GAT (EHW) 85/30
  • 85
  • 30
  • 7
  • 1.5
  • GAT (EHW) 100/38
  • 100
  • 38
  • 7
  • 1.5
  • GAT (WHW) 120/45
  • 120
  • 45
  • 7
  • 1.5
TECHNICAL SPECIFICATION
  • Properties
  • Value
  • Standard
  • Physical
  •  
  •  
  • Tensile Strength
  • 10 N/mm2 (MPA)(min.)
  • ASTM D638
  • Ultimate Elongation
  • 350% (Min.)
  • ASTM D638
  • Longitudinal Change
  • -10% (Max.)
  • ASTM D2671
  • Density
  • 1.20 ± 0.2 gm/cm3
  • ASTM D792
  • Hardness
  • 45 ? 10 Shore D
  • ASTM D2240
  • Water Absorption
  • 0.5 % (max.)
  • ASTM D570
  • Thermal
  •  
  •  
  • Accelerated Ageing
  • (120oC for 500 Hrs)
  • ASTM D2671
  • Tensile Strength
  • 8 N/mm2 (Mpa) (min.)
  • ASTM D 638
  • Ultimate Elongation
  • 250%(Min.)
  • ASTM D638
  • Low temperature Flexibility (-40oC for 4 Hrs.)
  • No Cracking
  • ASTM D2671
  • Heat Shock (250oC for 30 Min.)
  • No Cracking or flowing
  • ESI 09-11
  • Shrink Temperature
  • 125oC
  • IEC 216
  • Continuous Temperature limit
  • -40oC to + 110oC
  • IEC 216
  • Electrical
  •  
  •  
  • Dielectric Strength
  • 15 KV/mm. (Min.)
  • ASTM D149
  • Volume Resistivity
  • 1 x 1014 Ohm.cm(min.)
  • ASTM D257
  • Dielectric Constant
  • 5 (Max.)
  • ASTM D150
  • Resistant to track & erosion
  • No Tracking, erosion or flame failure upto 3.25 KV for 20 min.
  • ASTM D2303

Products